1KVA True Online UPS – Power Backup

SKU: RCT-1000GT
Availability:

In stock


Compare

EPS UPS – uninterruptible power supply, we provide a comprehensive range of systems from small stand-alone units, to large rackmount systems

Please login or register to see prices


This is our RRP. Please login or register an account for Dealer Pricing


In stock

Overview

True double Conversion

Wide input voltage range

Input power factor correction 0.99

Output Power Factor 0.8 50Hz/60Hz

Frequency converter mode

Emergency power off function (EPO)

Eco mode operation for energy saving (ECO)

Generator compatible

Charger capacity expansion to 8A for long run models

SNMP+USB+RS-232 multile communications

Smart battery charger design for optimized battery performance

Selectable output voltage: 208-240VAC, 110-127VAC

Optional rackmount form factor


Specifications

PHASE Single phase with ground

CAPACITY 1000 VA / 1200w

Voltage Range

Low Line Transfer 160 VAC ± 5% or 80 VAC ± 5% @ 100% load, 110 VAC ± 5% or 50 VAC ± 5% @ 50% load

Low Line Comeback 175 VAC ± 5% or 85 VAC ± 5% @ 100% load

High Line Transfer 300 VAC ± 5 % or 150 VAC ± 5 %

High Line Comeback 290 VAC ± 5 % or 145 VAC ± 5 %

Frequency Range 40 Hz ~ 70 Hz

Power Factor ≧ 0.99 @ nominal voltage (100% load)

AC Voltage Regulation (Batt. Mode) ± 3%

Frequency Range (Synchronized Range) 47 ~ 53 Hz or 57 ~ 63 Hz

Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz

Current Crest Ratio 03:01

Harmonic Distortion ≦ 4 % THD (Linear Load), ≦ 7 % THD (Non-linear Load)

THD (Linear Load) ≦ 6 % THD (Non-linear Load)

Transfer Time

AC Mode to Batt. Mode Zero

Inverter to Bypass 4 ms (Typical)

Waveform (Batt. Mode) Pure Sinewave

AC Mode 88%

Battery Mode 83%

Standard Model

Battery Type 12 V / 9 Ah

Numbers 6

Typical Recharge Time 4 hours recover to 90% capacity

Charging Current (max.) 1.0 A

Charging Voltage 82.1 VDC ±1%

Long-run Model

BatteryType Depending on applications

Numbers 6

Charging Current (max.) 8.0 A

Charging Voltage 82.1 VDC ±1%

LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

Battery Mode Sounding every 4 seconds

Low Battery Sounding every second

Overload Sounding twice every second

Fault Continuously sounding

Weight 15 kg
Dimensions 25 x 45 x 20 cm